Applications

Forced-flow circulation of sanitary blocks when not being used as intended - no consumption meter in floor

KEMPER KHS-hygiene flushing and KHS-Multi-Circ Distribution Unit in the riser branch

 

KHS-hygiene flushing is used in riser branch installations up to five floors and ten sanitary blocks. Two KHS-hygiene flushing systems each are recommended in the upper sanitary blocks. The flushing volume flow of 0.24 l/s (one KHS hygiene flushing = 0.12 l/s) is implemented independent of the precompression. At this volume flow, a sufficiently large flow velocity can be ensured to be able to flawlessly operate the piping system hygienically.

To achieve use of the CW system as intended, KHS-Multi-Circ Distribution Units are integrated in the CW riser branches. Based on their structure with simultaneous looping of all CW consumers they ensure there is a complete flow through of the sanitary block during flushing in normal operation (e.g., taking a shower). That also applies to a controlled flushing using KHS-hygiene flushing.

 

 

 

 

 

 

 

 

 

 

Automated riser branch flushing with consumption measurement
- e.g. apartment construction

 

Drinking water hygiene by flushing in the riser branch and continuous withdrawal in the sanitary blocks

 

 

Securely flow in the distribution and riser lines along with integrating suitable KEMPER KHS-VAV/-plus Maximum flow isolating ball valve with spring-reset servo drive actuators at the end of the branch ensures use as intended in the individual sanitary blocks by regularly activating the tapping points.

Recommendation:
To use the accruing flushing water, collect the water in a storage tank (e.g. systems for using rain water, watering outdoor facilities, etc.)

 

 

 

 

 

 

 

 

 

Forced-flow circulation of sanitary blocks for multi-storey buildings - without a consumption meter in floor

Operating method: time controlled flushing process

 

 

In the time-controlled flushing process, flushing can be present and logged on defined days of the week and at defined times (e.g., Monday 10 min. flush duration from 12 pm to 12:10 pm).

 

 

 

 

 

Operating method: volume controlled flushing process

 

Drinking water hygiene by periodically flushing the CDW system with a preset flush volume

 

 

In the volume-controlled flushing process, the KEMPER KHS-Logic Control System can be programmed to the calculated flushing volume. The entire CDW system can be flushed in that manner. For this system variant, the KHS-vortex flow sensor (with a measuring range of 5-100 l/min. or 10-200 l/min.) is needed in combination with one each terminal flushing valve (KHS-VAV-plus Maximum flow isolating ball valve with spring-reset servo drive).

 

 

 

 

 

 

 

Operating method: temperature controlled flushing process

Drinking water hygiene by flushing the CDW system up to temperature constancy at any desired point in the system

 

 

In the temperature-controlled flushing process, a reference temperature (e.g. at the CDW building connection) is constantly compared with several temperatures in the piping system (preferably in the feed line before the most remote sanitary blocks). The system control triggers flushing if the temperature difference exceeds the preset target temperature difference.

Example:
CDW at the building connection 15 °C, CDW most remote sanitary block 21 °C, default target temperature difference 3 K.

KHS-Logic Control System reaction
Flushing is triggered until the target temperature difference of 3 K is reached.

Result
CDW at the building connection 15 °C, CDW most remote sanitary block 18 °C

 

 

 

 

 

 

 

 

 

 

 

 

 

Flushing terminal or seldom-flowed pipeline sections

 

 

Drinking water hygiene by flushing terminal pipelines

 

Recommendation:
To use the accruing flushing water, collect the water in a storage tank (e.g. systems for using rainwater, watering outdoor facilities, etc.)

 


  • KEMPER HOTLINE
    Still questions?

  • Phone +49 27 61-8 91-0
    Fax +49 27 61-8 91-1 75